Description
Range | TeSys |
---|---|
Product name | TeSys D |
Device short name | LR97 |
Product or component type | Electronic overcurrent relay |
Relay application | Sensitivity to phase failure Overload Imax > Isetting Locked rotor, mechanical jamming I > 3 x Isetting |
Product compatibility | LC1D09...D38 |
Network type | AC |
[Us] rated supply voltage | 200...240 V AC |
Thermal protection adjustment range | 0.3…1.5 A |
[Ue] rated operational voltage | 600 V AC 50/60 Hz for power circuit conforming to CSA 600 V AC 50/60 Hz for power circuit conforming to UL 690 V AC 50/60 Hz for power circuit conforming to IEC 60947-4-1 |
Quantity per set | Set of 10 |
Network frequency | 50...60 Hz |
---|---|
Mounting support | Direct on contactor Rail |
Tripping threshold | 0.3...1.3 A |
Surge withstand | 6 kV conforming to IEC 61000-4-5 |
Contacts type and composition | 1 C/O |
[Ith] conventional free air thermal current | 3 A for control circuit |
Protection type | BS fuse 3 A - for control circuit GB2 circuit breaker 3 A - for control circuit GG fuse 3 A - for control circuit |
Maximum power | 28 W at 110 V DC conforming to IEC 60947 28 W at 220 V DC conforming to IEC 60947 55 W at 24 V DC conforming to IEC 60947 55 W at 48 V DC conforming to IEC 60947 140 VA at 48 V AC conforming to IEC 60947 360 VA at 110 V AC conforming to IEC 60947 360 VA at 220 V AC conforming to IEC 60947 70 VA at 24 V AC conforming to IEC 60947 |
[Ui] rated insulation voltage | Power circuit: 600 V conforming to CSA Power circuit: 600 V conforming to UL Power circuit: 690 V conforming to IEC 60947-4-1 |
[Uimp] rated impulse withstand voltage | 6 kV |
Phase failure sensitivity | < 3 s |
Reset | Automatic reset 120 s fixed Electrical by interruption of power supply for minimum 0.1 s Manual reset |
Time range | 0.2...10 s - O-time knob 0.3...10 s - O-time knob 0.5..30 s - D-time knob |
Signalling function | 2 LEDs |
Connections - terminals | Control circuit: cable 1 x 1…25 mm²flexible with cable end Control circuit: cable 1 x 1…25 mm²flexible without cable end Power circuit: cable 1 x 1…4 mm²flexible with cable end Power circuit: cable 1 x 1.5…10 mm²flexible without cable end Power circuit: lug-clamp 1 x 1…4 mm²flexible with cable end Power circuit: lug-clamp 1 x 1.5…10 mm²flexible without cable end Control circuit: cable 2 x 1…25 mm²flexible with cable end Control circuit: cable 2 x 1…25 mm²flexible without cable end Control circuit: lug-clamp 1 x 1…25 mm²flexible with cable end Control circuit: lug-clamp 1 x 1…25 mm²flexible without cable end Control circuit: lug-clamp 2 x 1…25 mm²flexible with cable end Control circuit: lug-clamp 2 x 1…25 mm²flexible without cable end |
Tightening torque | Control circuit: 0.6...1.2 N.m on lug-clamp Power circuit: 2 N.m on cable |
height | 67.5 mm |
Width | 45 mm |
Depth | 67.5 mm |
Net weight | 0.172 kg |
standards | IEC 60255-6 IEC 60947 |
---|---|
product certifications | CSA UL GOST |
Protective treatment | TH conforming to IEC 60068 |
IP degree of protection | IP20 conforming to IEC 60529 |
Ambient air temperature for operation | -25…60 °C conforming to IEC 60947-4-1 |
Ambient air temperature for storage | -30…80 °C |
Operating altitude | 2000 m |
Fire resistance | 850 °C conforming to IEC 60695-2-1 |
Shock resistance | 15 gn 11 ms conforming to IEC 60068-2-7 |
Vibration resistance | 4 gn conforming to IEC 60068-2-6 |
Dielectric strength | 2 V 50 Hz conforming to IEC 60255-5 |
Resistance to electrostatic discharge | 6 kV in indirect mode 8 kV in air |
Resistance to radiated fields | 10 V/m level 3 |
Resistance to fast transients | 2 kV |
Disturbance radiated/conducted | 10 V conforming to EN 61000-4-6 Class A conforming to EN 55011 |